PP-010-RBG14-QFPKG/US/ /V
HÃY LIÊN HỆ VỚI CHÚNG TÔI ĐỂ ĐƯỢC HỖ TRỢ GIÁ TỐT NHẤT
THÔNG TIN SẢN PHẨM:
| Product characteristics | ||||
| Electronic pressure sensor | ||||
| Quick disconnect | ||||
| Adjustment of the switch point by teach function | ||||
| Process connection: G ¼ A / M5 I | ||||
| 2 outputs OUT1 = switching output OUT2 = switching output or diagnostic output | ||||
| Measuring range: -1...10 bar / -14.5...145 psi / -0.1...1.0 MPa |
| Application | Type of pressure: relative pressure Liquids and gases | |||
| Pressure rating | 75 bar | 1087 psi | 7.5 MPa | |
| Bursting pressure min. | 150 bar | 2175 psi | 15 MPa | |
| Medium temperature [°C] | -25...90 | |||
| Electrical data | ||||
| Electrical design | DC PNP | |||
| Operating voltage [V] | 9.6...36 DC ¹) | |||
| Current consumption [mA] | < 45 | |||
| Insulation resistance [MΩ] | > 100 (500 V DC) | |||
| Protection class | III | |||
| Reverse polarity protection | yes | |||
| Outputs | ||||
| Output | 2 outputs OUT1 = switching output OUT2 = switching output or diagnostic output | |||
| Output function | 2 x normally open / closed programmable or 1 x normally open / closed programmable + 1 x normally closed (diagnostic function) | |||
| Current rating [mA] | 2 x 250 | |||
| Voltage drop [V] | < 2 | |||
| Short-circuit protection | yes (non-latching) | |||
| Overload protection | yes | |||
| Switching frequency [Hz] | 170 | |||
| Measuring / setting range | ||||
| Measuring range | -1...10 bar | -14.5...145 psi | -0.1...1.0 MPa | |
| Setting range | ||||
| Set point, SP | -0.90...10.00 bar | -13...145 psi | -0.090...1.000 MPa | |
| Reset point, rP | -0.95...9.95 bar | -14...144 psi | -0.095...0.995 MPa | |
| in steps of | 0.05 bar | 1 psi | 0.005 MPa | |
| Factory setting | SP1 = 2.50 bar; rP1 = 2.30 bar SP2 = 7.50 bar; rP2 = 7.30 bar OUT1 = Hno; OUT2 = Hno | |||

Product characteristics